Two persons are required to move a power unit. Keep the power unit and bypass
unit horizontal during movement.
Figure 4-17 Removing the power unit and bypass unit
Step 3 Install guide rails (2 U) on the rack.
1. Align the lower edge of the guide rail with the lower edge of a U scale, and
then engage the mounting ears on both ends of the guide rail into the
mounting holes.
NO TICE
Ensure that the lower edge of the guide rail is aligned with the lower edge of
a U scale.
UPS5000-A-(30 kVA-120 kVA)
User Manual 4 Installation and Cable Connection
Issue 17 (2024-02-21) Copyright © Huawei Digital Power Technologies Co., Ltd. 81