NO TE
The RS485_R DIP switch is used to enable a build-out resistor so that the ambient T/H
sensor can communicate with the controller. If there are no more than four ambient T/H
sensors on the bus, the RS485_R DIP switch does not need to be set. If there are more than
four, ip the RS485_R DIP switch of the ambient T/H sensor furthest from the UPS to ON.
DIP switch settings on ambient T/H sensors
Each ambient T/H sensor has a unique DIP switch address, ranging from 32 to 44.
A DIP switch has six binary toggle switches. The bit on the leftmost is the most
signicant bit, and the bit on the rightmost is the least signicant bit. Bit 1
indicates ON, and bit 0 indicates OFF.
Table 5-1 Mapping between DIP switch positions and addresses (ambient T/H
sensor)
No. RS485 Address
32 33 34 35 36 37 38 39 40 41 42 43 44
6 1 1 1 1 1 1 1 1 1 1 1 1 1
5 0 0 0 0 0 0 0 0 0 0 0 0 0
4 0 0 0 0 0 0 0 0 1 1 1 1 1
3 0 0 0 0 1 1 1 1 0 0 0 0 1
2 0 0 1 1 0 0 1 1 0 0 1 1 0
1 0 1 0 1 0 1 0 1 0 1 0 1 0
DIP switch settings on battery temperature sensors
When an ambient T/H sensor is used as a battery temperature sensor, set the DIP
switch to a value in the range of 16 to 28 to monitor the battery temperature.
Table 5-2 DIP switch address mapping (battery temperature sensor)
No
.
RS485 Address
16 17 18 19 20 21 22 23 24 25 26 27 28
6 0 0 0 0 0 0 0 0 0 0 0 0 0
5 1 1 1 1 1 1 1 1 1 1 1 1 1
4 0 0 0 0 0 0 0 0 1 1 1 1 1
3 0 0 0 0 1 1 1 1 0 0 0 0 1
2 0 0 1 1 0 0 1 1 0 0 1 1 0
1 0 1 0 1 0 1 0 1 0 1 0 1 0
UPS5000-A-(30 kVA-120 kVA)
User Manual 5 Single UPS Commissioning
Issue 17 (2024-02-21) Copyright © Huawei Digital Power Technologies Co., Ltd. 125