4 Installation and Cable Connection
4.1 Installation Preparations
4.1.1 Site Planning
Installation Environment
● Do not install the UPS in a high-temperature, low-temperature, or damp place
that is beyond the technical specications.
● Install the UPS away from water sources, heat sources, and ammable or
explosive materials. Install the UPS in an environment free of dust, volatile
gas, salt, and corrosive materials. Avoid direct sunlight.
● Do not install the UPS in environments with conductive metal scraps in the
air.
● The optimal operating temperatures for valve-regulated lead-acid (VRLA)
batteries are 20–30°C. Operating temperatures higher than 30°C shorten the
battery lifespan, and operating temperatures lower than 20°C reduce the
battery backup time.
Clearances
Reserve sucient clearances around the cabinet to facilitate operations and
ventilation:
● Reserve a clearance of at least 800 mm from the front of the cabinets for
ventilation and operations.
● Reserve a clearance of at least 300 mm from the top of the cabinets for
operations.
● Reserve a clearance of at least 300 mm from the rear of the cabinets for
ventilation. Reserve a clearance of at least 800 mm if you need to perform
operations at the rear of the cabinet.
The gure uses a 30 kVA/40 kVA UPS as an example.
UPS5000-A-(30 kVA-120 kVA)
User Manual 4 Installation and Cable Connection