Item Specications
Rated frequency 50/60 Hz
Input frequency 40–70 Hz
Input power factor > 0.99 at full load; > 0.98 at half load
THDi THDi < 3% (linear load)
THDi < 5% (non-linear load)
Remarks:
1. The preceding specications are met when the mains input and bypass
input share a power source.
2. The input THDu is less than 1%.
Overvoltage
category
OVC II
3.6 Bypass Input Electrical Specications
Item
Specications
Input system Three-phase, four-wire, and PE
Rated input voltage 380 V AC/400 V AC/415 V AC (line voltage)
Rated frequency 50/60 Hz
Frequency range ±6 Hz (adjustable, 0.5–6 Hz, ±2 Hz by default)
Input system The mains input and bypass input can share a power source or use
dierent power sources.
Overvoltage category OVC II
3.7 Battery Specications
UPS5000-A-(30 kVA-120 kVA)
User Manual 3 Technical Specications
Issue 17 (2024-02-21) Copyright © Huawei Digital Power Technologies Co., Ltd. 56