Item Specications
Total
harmonic
distortion of
output
voltage
(THDv)
● ≤ 1% (100% linear load)
● ≤ 4% (100% non-linear load)
Output
power
factor
● UPS5000-A-30KTTL/UPS5000-A-40KTTL/UPS5000-A-80KTTL/UPS5000-
A-60KTTL/UPS5000-A-120KTTL: 1
● UPS5000-A-60KTTL-H/UPS5000-A-120KTTL-H: 0.9
Transfer
time
● Normal mode: 0 ms uninterrupted transfer; ≤ 20 ms interrupted transfer
● ECO mode: 4 ms under typical working conditions; ≤ 20 ms under other working
conditions
Output
voltage
unbalance
±3%
Inverter
overload
capability
● UPS5000-A-30KTTL/UPS5000-A-40KTTL/UPS5000-A-80KTTL/UPS5000-
A-60KTTL/UPS5000-A-120KTTL:
– 100% < load ≤ 110%: transfer to bypass mode after 60 min
– 110% < load ≤ 125%: transfer to bypass mode after 10 min
– 125% < load ≤ 150%: transfer to bypass mode after 1 min
– Load > 150% or a short circuit occurs: run for 200 ms
● UPS5000-A-60KTTL-H/UPS5000-A-120KTTL-H:
– 100% < linear load ≤ 110%: transfer to bypass mode after 60 min
– 110% < linear load ≤ 125%:
– 0–30°C: transfer to bypass mode after 10 min
– 30–40°C: transfer to bypass mode after 3 min
– 125% < load ≤ 150%: transfer to bypass mode after 30s
– Load > 150% or a short circuit occurs: run for 200 ms
Inverter
output
short-circuit
capability
151 A
3.9 System Electrical Specications
Item
Specications
Parallel system
reliability
Redundancy design for parallel signals
UPS5000-A-(30 kVA-120 kVA)
User Manual 3 Technical Specications
Issue 17 (2024-02-21) Copyright © Huawei Digital Power Technologies Co., Ltd. 58