Identier Type Working
Principle
Signal
Description
Status
Description
System Action
SWITCH
STATUS_BP
DI Port for
monitoring
the PDC
bypass input
switch status
(This port can
also be
dened as the
port for
monitoring
the system
maintenance
switch status
on the UI.)
The default value
is Closed:
● BP port closed:
The bypass
input switch or
system
maintenance
switch is ON.
● BP port open:
The bypass
input switch or
system
maintenance
switch is OFF.
The value can be
changed to Open:
● BP port open:
The bypass
input switch or
system
maintenance
switch is ON.
● BP port closed:
The bypass
input switch or
system
maintenance
switch is OFF.
PDC bypass
input switch:
After the setting
takes eect, the
system will
generate a PDC
bypass input
open alarm.
System
maintenance
switch: After the
setting takes
eect, the
system will
generate a
system
maintenance
bypass circuit
breaker closed
alarm and
transfer to static
bypass mode.
SWITCH
STATUS_0V
Port for signal
ground
EPO_12V DI +12V If the NO signal
port is connected
to the EPO_12V
port, EPO is
triggered.
After the setting
takes eect, the
system will
generate an EPO
alarm and stop
supplying power.
EPO_NO If the NO
signal port is
connected to
the EPO_12V
port,
emergency
power-o
(EPO) is
triggered.
 
When connecting the dry contact signal cable of an external device to a UPS dry contact,
ensure that the silk screens of the dry contacts at both ends of the cable are consistent.
UPS5000-A-(30 kVA-120 kVA)
User Manual 2 Product Overview
Issue 17 (2024-02-21) Copyright © Huawei Digital Power Technologies Co., Ltd. 45