Item 30
kVA
40 kVA 60 kVA 80
kVA
120 kVA
N (When
the UPS
connects
to a non-
linear
load,
increase
the cross-
sectional
area.)
Battery
input
Nominal battery
discharge current (A)
82 110 UPS5000-
A-60KTTL-H:
118
UPS5000-
A-60KTTL: 164
219 UPS5000-
A-120KTTL-H:
236
UPS5000-
A-120KTTL:
329
Battery maximum
discharge current (A)
98 131 UPS5000-
A-60KTTL-H:
142
UPS5000-
A-60KTTL: 197
262 UPS5000-
A-120KTTL-H:
284
UPS5000-
A-120KTTL:
394
Recomme
nded
cross-
sectional
area
(mm
2
)
+ 3 x 16 3 x 35 3 x 70 3 x 95 3 x 150
N
-
Ground
cable
Recomme
nded
cross-
sectional
area
(mm
2
)
PE 1 x 10 1 x 16 1 x 16 1 x 25 1 x 50
UPS5000-A-(30 kVA-120 kVA)
User Manual 4 Installation and Cable Connection
Issue 17 (2024-02-21) Copyright © Huawei Digital Power Technologies Co., Ltd. 67