Table 4-2 Power cable terminal requirements
Model Port Connection Method Bolt
Specications
Bolt Hole
Diameter
Torque
30–40 kVA Mains
input
Crimped OT terminal M6 6.5 mm 4.5 N·m
60–80 kVA Crimped DT terminal M8 9 mm 13 N·m
120 kVA Crimped DT terminal M10 11 mm 27 N·m
30–40 kVA Bypass
input
Crimped OT terminal M6 6.5 mm 4.5 N·m
60–80 kVA Crimped DT terminal M8 9 mm 13 N·m
120 kVA Crimped DT terminal M10 11 mm 27 N·m
30–40 kVA Battery
input
Crimped OT terminal M8 9 mm 13 N·m
60–80 kVA Crimped DT terminal M10 11 mm 27 N·m
120 kVA Crimped DT terminal M12 13 mm 47 N·m
30–40 kVA Output Crimped OT terminal M6 6.5 mm 4.5 N·m
60–80 kVA Crimped DT terminal M8 9 mm 13 N·m
120 kVA Crimped DT terminal M10 11 mm 27 N·m
30–40 kVA PE Crimped OT terminal M6 6.5 mm 4.5 N·m
60–120
kVA
Crimped DT terminal M8 9 mm 13 N·m
Figure 4-2 OT terminal
UPS5000-A-(30 kVA-120 kVA)
User Manual 4 Installation and Cable Connection
Issue 17 (2024-02-21) Copyright © Huawei Digital Power Technologies Co., Ltd. 69