EasyManua.ls Logo

Huawei UPS5000-E-200K-SM - Page 297

Huawei UPS5000-E-200K-SM
300 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
C Alarm List
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
288
Alarm
ID
(Alarm
ID-Caus
e ID)
Alarm
Name
Severit
y
Cause
Solution
length of
the bypass
input or
output
cables is
incorrect.
The
bypass
SCR
open-circ
uits.
3. Rectify any bypass SCR
open-circuit.
0150-1
Inverter
asynchrono
us
Minor
The
bypass
frequency
changes
fast.
The
output
frequency
track rate
is
incorrectl
y set.
1. Check that the bypass output
frequency does not change fast.
2. Check that the Output freq.
track rate is properly set.
0101-1
BSC signal
abnormal
Minor
The dual
bus
connector
is loose.
Parameter
s are set
incorrectl
y.
1. Check the dual bus connector.
2. Check the parameter settings.
0102-1
Maint.
breaker
misoperatio
n
Critical
The user
operation is
incorrect.
1. Shut down the inverter and then
close the maintenance circuit
breaker.
2. After maintenance, open the
maintenance circuit breaker and
then start the inverter.
0380
In
self-check
Warning
The inverter
is in
self-check.
Wait until the inverter self-check is
complete.

Table of Contents

Other manuals for Huawei UPS5000-E-200K-SM

Related product manuals