EasyManua.ls Logo

Hukseflux SR05 series - 6.5 Network Communication: Getting Started; 6.5.1 Adapting Modbus Address and Communication Settings

Hukseflux SR05 series
83 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SR05-D1A3-PV manual v1801 53/83
6.5 Network communication: getting started
Once it has the correct Modbus address and communication settings, SR05-D1A3-PV can
be connected directly to an RS-485 network and a power supply. How to physically
connect a sensor as a slave in a Modbus network is shown in section 5.11: Connecting a
SR05-D1A3-PV to an RS-485 network. In such a connection the sensor is powered via an
external power supply of 5 to 30 VDC. When the sensor is bolted onto a grounded
mounting plate, which is usually the case, the shield is not connected to ground at the
cable end.
Installing a SR05-D1A3-PV in the network also requires configuring the communication
for this new Modbus device. This usually consists of defining a request that can be
broadcast by the master. If the SR05-D1A3-PV is not already defined as a standard
sensor type on the network, contact the supplier of the network equipment to see if a
library file for the SR05-D1A3-PV is available.
Typical operation requires the master to make a request of irradiance data in registers
0x1002 + 0x1003, sensor temperature in register 0x1006, and the sensor serial number
in register 0x1028 every 1 second, and store the 60 second averages. The data format of
register 0x1002 + 0x1003 is a signed 32 bit integer and the temperature in register
0x1006 is a signed 16 bit integer.
Up to five 16 bit registers can be requested in one request. In case six or more registers
are requested in just one request, SR05-D1A3-PV will not respond. If requesting six or
more registers, multiple requests should be used: SR05-D1A3-PV will respond as
expected.
6.5.1 Adapting Modbus address and communication settings
Setting the instrument address and baud rate can be done in different ways:
by connecting the sensor to the PC and using the Sensor Manager;
by connecting the sensor to the PC and using another Modbus testing tool. There are
links to different solutions available at www.modbus.org
;
by using the available network user interface software.
The Modbus address is stored in register 0x1000 and has a default value of 1. A user
may change the address to a value in the range of 1 to 247. The address value must be
unique in the network. The communication settings are stored in register 0x1001. The
default setting is setting number 1 representing a communication with 9600 baud, no
parity bit, 8 data bits and 1 stop bit. After a new address or communication setting is
written the sensor must be restarted. This can be done by writing 0XFF00 to coil 0.

Table of Contents