8.1.2 Electrode Wear
Electrode wear is dependent on:
feed water quality (conductivity and hardness) and
generated amount of steam.
Attention: The electrodes must be exchanged at the latest if the
display shows the message Service (red LED is blinking). The
unit is switched off in case it senses a period of one hour's oper-
ation in the "Cylinder full" condition. As a guide they must still be
a third to one half their original length.
The original length of HygroMatik stainless steel large-area elec-
trodes is as follows:
Uneven Electrode Wear
Replace badly worn electrodes completely. Check main fuses !
If a main fuse has blown the corresponding electrode will not be
supplied with power and hence will not wear.
Type lenght [mm]
C01KIT 115
C02KIT 80
C06KIT 125
C10KIT 155
C17KIT-C45KIT 235