15
Table 5.6 Possible multi-unit configurations
Mode Phase Description
Single-phase
120V 60Hz
Single Unit 120V/60Hz, 25A
Multi (N) Units N≤12
120V/60Hz, 25A x N
(Stack Power & current)
Split-phase
240V 60Hz
P1 (Phase 1) x N Units N≤6
Line 1, 120V/60Hz, 25A x N
(Stack Power & current)
P2 (Phase 2) x N Units N≤6
Line 2, 120V/60Hz, 25A x N
(Stack Power & current)
3-phase
208V 60Hz
P1 (Phase 1) x N Units N≤4
Line 1, 120V/60Hz, 25A x N
(Stack Power & current)
P2 (Phase 2) x N Units N≤4
Line 2, 120V/60Hz, 25A x N
(Stack Power & current)
P3 (Phase 3) x N Units N≤4
Line 3, 120V/60Hz, 25A x N
(Stack Power & current)
Note: N = Number of Apollo 5K units
5.4 Multi-unit Setup
This section provides wiring diagrams for a multi-unit setup. The Apollo 5K
supports up to 12 units (36KW) working synergically for single-phase,
split-phase or 3-phase power supply.
Important! Additional accessories are needed for setting up the Apollo 5K
multi-unit system. They may be supplied by a qualified electrician. Hysolis
split-phase and single-phase parallel accessories are available for purchase.
Possible configurations include (Table 5.6):
• Up to 12 units can be stacked in parallel for Single-phase
• Up to 6 units for each of the Lines 1 and 2 for Split-Phase
• Up to 4 units each for the lines 1, 2, and 3 for 3-phase.
Note: Each Apollo has a maximum output of 25A. Each line has a maximum
current of 25A x N. Up to 12 units can be configured into Single-phase,
Split-phase, or 3-phase AC Output.