Ensure that there are little-to-no empty U-levels between devices installed in the rack cabinet
below the 32U level, unless the received conguration specically allowed it.
If the rack cabinet you are relocating is part of a suite of rack cabinets, detach the rack cabinet
from the suite.
If the rack cabinet you are relocating was supplied with removable outriggers they must be
reinstalled before the cabinet is relocated.
Inspect the route that you plan to take to eliminate potential hazards.
Verify that the route that you choose can support the weight of the loaded rack cabinet. Refer to
the documentation that comes with your rack cabinet for the weight of a loaded rack cabinet.
Verify that all door openings are at least 760 x 2083 mm (30 x 82 in.).
Ensure that all devices, shelves, drawers, doors, and cables are secure.
Ensure that the four leveling pads are raised to their highest position.
Ensure that there is no stabilizer bracket installed on the rack cabinet during movement.
Do not use a ramp inclined at more than 10 degrees.
When the rack cabinet is in the new location, complete the following steps:
Lower the four leveling pads.
Install stabilizer brackets on the rack cabinet or in an earthquake environment bolt the rack to
the floor.
If you removed any devices from the rack cabinet, repopulate the rack cabinet from the lowest
position to the highest position.
If a long-distance relocation is required, restore the rack cabinet to the conguration of the rack
cabinet as you received it. Pack the rack cabinet in the original packaging material, or equivalent.
Also lower the leveling pads to raise the casters off of the pallet and bolt the rack cabinet to the
pallet.
(R002)
(L001)
DANGER:
Hazardous voltage, current, or energy levels are present inside any component that has
this label attached. Do not open any cover or barrier that contains this label. (L001)
(L002)
DANGER:
Rack-mounted devices are not to be used as shelves or work spaces. Do not place
objects on top of rack-mounted devices. In addition, do not lean on rack-mounted devices and do
not use them to stabilize your body position (for example, when working from a ladder). Stability
hazard:
The rack may tip over causing serious personal injury.
Before extending the rack to the installation position, read the installation instructions.
viii Power Systems: Servicing the IBM Power Systems HMC (7063-CR2)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IBM 7063-CR2 and is the answer not in the manual?

IBM 7063-CR2 Specifications

General IconGeneral
BrandIBM
Model7063-CR2
CategoryNetwork Hardware
LanguageEnglish

Related product manuals