EasyManua.ls Logo

iC-Haus iC-TW29 - ZERO Inputs

iC-Haus iC-TW29
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
preliminary preliminary
iC-TW29 26-BIT ENCODER PROCESSOR
WITH INTERPOLATION AND BiSS INTERFACE
Rev C1, Page 23/28
SIN+
SIN–
COS+
COS–
iC-TW29
AVDD
PSIN
NSIN
PCOS
NCOS
iC-SMxL
Sensor
Figure 18: Magnetic Sensor Connection
SIN+
SIN–
COS+
COS–
iC-TW29
5V
PA
NA
PB
NB
iC-PT…H
Sensor
ZERO+PZ
ZERO–NZ
Figure 19: Optical Sensor Connection
Nominal differential signal amplitudes between 20 mV
and 2.0 V in two ranges can be accommodated.
ZERO Inputs
The iC-TW29 can interface to a wide range of differen-
tial or single-ended index or zero sensors to provide a
Z output which is synchronized with the AB outputs or
to reset the gearbox counter. Optical sensors usually
provide differential zero or index signals along with the
sin/cos signals. In magnetic systems, a separate zero
sensor is usually required.
Digital zero sensors (Hall, MR, and others) typically pro-
vide a single-ended active-low signal via an open-drain
output that pulls low in the presence of a magnetic eld.
Connect active-low (open drain) digital index sensors to
the iC-TW29 ZERO– input and connect the ZERO+ in-
put to VDD/2 using a resistive voltage divider as shown
in Figure 20.
ZERO+
ZERO-
DVDD
iC-TW29
Digital Hall
active low
AVDD
Figure 20: Digital Index Sensor Connection
Analog-output zero sensors, such as MR bridges, can
also be used with the iC-TW29 as shown in Figure 21.
iC-TW29
MR Index
Sensor
ZERO+
ZERO-
Figure 21: Analog Index Sensor Connection
To produce a Z output once every input cycle, connect
ZERO+ to 3.3 V and ZERO– to ground. This is use-
ful in on-axis applications where one input revolution
produces only one input cycle.
If no Z output from the iC-TW29 is required, connect
ZERO+ to ground and ZERO– to 3.3 V.