EVOMAX - Installation & Servicing
INSTALLATION
206210-5359b
21

The maximum ue extension for an Evomax 30 on open ue is 65m. Therefore
this installation is acceptable.
Example 3
22

The total maximum ue resistance for an Evomax 120 is 288 Pa or
17.6m 100/150. Therefore this installation is acceptable.
Example 4
FLUE OUTLET
Horizontal Flue for Evomax 120
Resistance (Pa) Resistance (m)
Flue Size 100/150 100/150
Horizontal Wall Flue Kit 100/150 100 3.3
2 x 1m extension ue 2 x (16.4) 2 x (1)
1 x 90º elbow 50 2
Total Flue Resistance 183 7.3
Open Flue for Evomax 30
Resistance (m)
Flue Size 80
5 x 1m extension 5 x 1
2 x 45º elbow 2 x 0.6
Total Flue Resistance 6.2
206210-5357b
206210-3.indd 18 09/06/2011 13:34:23