LOCATION 35 Second Loop Response Time
The first and second loop response times are two preset delay periods that are initiated by the options
selected in locations 1 to 32, sub-location 2, bit 5.
0 6 ms 8 96 ms
1 12 ms 9 108 ms
2 24 ms (default) 10 120 ms
5 60 ms 13 156 ms
6 72 ms 14 168 ms
7 48 ms 15 180 ms
This location defines the cross-zone delay timer period.
0 3 seconds
1 10 seconds
2 15 seconds
3 20 seconds (default)
Cross-Zone Count (Default = 2)
If the panel is armed and the total number of violations of zones programmed as cross-zones reaches
this count within the time period programmed into location 36, an alarm condition will be registered.
Program a value from [0] to [1] [5]. A [0] will disable this location. Program zones as cross-zones in sub-
location 2 of locations 1 to 16. Any single zone enabled for cross zoning, which is violated continuously
for the time specified in Location 36 will also register an alarm condition.