attempt to report to the primary number fails. In either case, the number of attempts (per phone
number) will be equal to the number stored in location 115, with a default value of 6.
The primary and secondary telephone numbers may be joined to provide for a single telephone
number of 48 digits in length.
LOCATION 112 Auto Test Interval
The value programmed into this location will determine the duration of time between Auto Tests.
LOCATION 113 Auto Test Time
Enter the time when the auto test will be reported. The format is “hhmm” based on a 24 hour clock. (All
four digits must be entered.)
Example:
If a value of [7] was programmed into location 112 and [1400] was programmed into this location, the
auto test would be sent weekly at 2:00pm.
LOCATION 114 Number of Account Code Digits (Default = 4)
Most reporting formats use a 4 digit account code. Program a 6 into this location to enable six digit
account code reporting.
LOCATION 115 Number of Dial Attempts (Default = 6)
This location determines the maximum number of dial attempts that the panel will make in order to
contact the base station.
NOTE:
Entering [0] into this location will disable the dialler.