Location 142: Zone Trip Count
This and location 143 are also known as “double knock” by some. What this means is that, if a follower
zone trips this many times, while the system is armed, in the time entered into location 143.
Location 143: Zone Trip Count Time Delay
The zone must trigger the number of times set in location 142, within the time period set in this location.
Note: Value range is 0 to 15. The number entered will be multiplied by 10 to give the seconds.
Example: Location 142 has a 2 in it. Location 143 has a 3.
From the above example, time period that the violations must happen for the alarm to trigger is 3 x 10 =
30 seconds. Therefore the zone must trigger twice within 30 seconds before the system will register an
alarm.
Location 144: Trouble Display
This location is a choice of displaying a trouble condition if a fault occurs for telephone line monitoring
and a siren tamper. Both or either can be displayed.
Telephone Line
Monitoring Fail
The 805s will ignore the Telephone Line Monitoring trouble as there is no dialler.
Location 145: Trouble Display 2
Communication fail, Keypad tamper and engineer reset are the three choices.
Location 146: Keypad Sleep Delay
Choose the value that represents the time for the keypad to wait before switching all LEDs off.