9.4 Settings for temperature monitoring
9.4.1 Settings for limit value monitoring with OUT2
Select [SEL2] and set [TEMP]�
Select [OU2] and set the switching function�
- [Hno] = hysteresis function/NO
- [Hnc] = hysteresis function/NC
- [Fno] = window function/NO
- [Fnc] = window function/NC
Select [SP2] and set the value at which the output switches�
Select [rP2] and set the value at which the output switches back�
9.4.2 Setting the analogue value for temperature
Select [SEL2] and set [TEMP]�
Select [OU2] and set the function�
- [I] = temperature-proportional current signal (4…20 mA)
Select [ASP] and set the value at which the minimum value is provided�
Select [AEP] and set the value at which the maximum value is provided�
9.5 User settings (optional)
9.5.1 Setting of the standard unit of measurement for volumetric flow
Select [Uni] and set the unit of measurement�
- [Lmin] = volumetric flow quantity in standard litres / minute
- [nm3h] = volumetric flow quantity in standard cubic metres / hour
- [nmS] = current flow velocity in standard metres / second
The setting only has an effect on the volumetric flow value�
9.5.2 Configuration of the standard display
Select [SELd] and determine the standard measuring unit�
- [FLOW] = the current volumetric flow value in the standard unit of
measurement is displayed
- [TOTL] = the current meter reading in Nm
3
or 1000 Nm
3
is displayed�
- [TEMP] = the current medium temperature in °C is displayed
Select [diS] and set the update rate and orientation of the display
- [d1] = update of the measured values every 50 ms
- [d2] = update of the measured values every 200 ms
- [d3] = update of the measured values every 600 ms
- [rd1], [rd2], [rd3] = display as for d1, d2, d3; rotated by 180°
- [OFF] = the display is switched off in the operating mode; when press-
ing the button the process value is displayed for 15 s�