9.3 Explanation of the menu
SP1/rP1 Upper / lower limit value for the level at which OUT1 switches�
FH1/FL1 Upper / lower limit for the acceptable range (monitored by OUT1)�
SP2/rP2 Upper / lower limit value for the level at which OUT2 switches�
FH2/FL2 Upper / lower limit for the acceptable range (monitored by OUT2)�
SP3/rP3 Upper / lower limit value for the level at which OUT3 switches�
FH3/FL3 Upper / lower limit for the acceptable range (monitored by OUT3)�
SP4/rP4 Upper / lower limit value for the level at which OUT4 switches�
FH4/FL4 Upper / lower limit for the acceptable range (monitored by OUT4)�
OUx Output function for OUTx:
Switching signal for the level limit values: hysteresis function [H ��] or window
function [F ��], either normally open [� no] or normally closed [� nc]�
OFS Offset value for level measurement�
EF Extended functions / opening of menu level 2�
rES Restore factory setting�
dr1 Switch-off delay for OUT1� The menu item is only active if
OU1 = Hno or Hnc�
dr2 Switch-off delay for OUT2� The menu item is only active if
OU2 = Hno or Hnc�
dr3 Switch-off delay for OUT3� The menu item is only active if
OU3 = Hno or Hnc�
dr4 Switch-off delay for OUT4� The menu item is only active if
OU4 = Hno or Hnc�
FOUx Response of OUTx in case of a fault�
dFo Delay time for switching response OUTx in case of a fault�
Uni Unit of measurement (cm or inch)�
SELd Type of indication�
LEnG Probe length�
MEdI Medium to be detected�
Prob Type of probe used (single probe or coaxial probe)� The menu item is only
active if MEdI = HIGH�
bin Changing between switching mode and binary mode�