44
• If the level is below SP1, the output is switched� If the level is above SP1 or if
there is a wire break, output 1 switches OFF (alarm message "overflow / wire
break")�
• If the level exceeds SP2, output 2 switches (upper value exceeded,
submersible pump ON)�
• If the level is below SP3, output 3 switches (lower value reached, submersible
pump OFF)�
15 Factory setting
Factory setting User setting
SP1 / FH1 25% SP/FHmax
rP1 / FL1 25% rP/FLmax
OU1 Hno
SP2 / FH2 50% SP/FHmax
rP2 / FL2 50% rP/FLmax
OU2 Hno
SP3 / FH3 75% SP/FHmax
rP3 / FL3 75% rP/FLmax
OU3 Hno
SP4 / FH4 100% SP/FHmax
rP4 / FL4 100% rP/FLmax
OU4 Hnc
OFS 0.0
dr1 0.0
dr2 0.0
dr3 0.0
dr4 0.0
FOU1 OFF
FOU2 OFF
FOU3 OFF
FOU4 OFF
dFo 0
Uni cm