11.4 Error indications
Possible cause Recommended measures
[E�000] Fault in the electronics� Replace the unit�
[E�031]
Probe detached from the unit;
possibly incorrect setting of the
probe length�
Check whether the probe is still
attached to the unit�
Check the parameter [LEnG]�
[E�033]
Measurement disturbed by
heavy foam formation or
turbulence�
• Install the unit in a still pipe or bypass�
• Set or increment [dFo] (→ 10.6.6)�
Measurement disturbed by
separation layers (e�g� oil layer
on water)�
Remove the oil layer by suction, stir the
medium, verify the composition�
Rod or process connection
soiled�
Clean the rod and the process
connection, carry out a reset�*
Installation conditions were not
adhered to�
Observe the notes in "Installation"
(→ 6)�
Probe length, type of probe
or sensitivity (setting to the
medium) is incorrect�
Correct the settings (→ 10.2), then
carry out a reset�*
[SCx]
Flashing: short circuit in
switching output x�
Remove the short circuit�
[SC]
Flashing: short circuit in all
switching outputs�
Remove the short circuit�
[PArA] Faulty data set Reset to factory settings (→ 10.7)�
* Carry out a reset (power off and on again) after rectifying the fault to reset the error
message�