EasyManua.ls Logo

IMO Precision Controls Jaguar VXS - 7.2 Descriptions of Functions

Default Icon
67 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
26
When Function 00 = 1, all data becomes
‘read-only’. To change Function 00, simulta-
neously press the STOP key and either or ∨.
Refer also to Function 57 — special use of
terminal THR to protect Function data.
Jaguar VXS inverters can be controlled entirely
at the keypad, or by inputs to control terminals
only, or by a combination of keypad inputs and
terminal inputs. (Refer to Function 02.)
As delivered from the factory, Function 01 = 0.
It cannot be changed while the link at terminals
FWD-P24 is in place. If the link has been
removed and replaced by an external FWD
and/or REV control circuit, the contacts must be
of the normally-open type.
When Function 01 = 0, the frequency refer-
ence input is provided at the keypad, using the
and keys.
When Function 01 = 1, the and keys are
disabled and the frequency input reference is
provided by voltage and/or current input refer-
ence signals at terminals 12 and C1. (Refer to
pages 14 and 15).
NOTE If both a voltage and a current input
reference signal are applied, the input
reference is the sum of the two.
Motorised pot. mode
When Function 01 = 2 or 3, the inverter
responds to commands at terminals
FWD/REV-P24, X1-P24 and X2-P24 as
shown in the example diagrams below. When
FWD/REV-P24 is OFF (STOP command), the
next initial frequency is either zero (F01 = 2)
or is the last previous frequency (F01 = 3).
Accel/decel 2 can be applied by X4-P24.
Refer to Function 43.
NOTE Output frequency may be further
modified by Functions 34 and 35.
7.2 Descriptions of Functions
00 Data protection
Title boxes with a heavy type and border indicate Functions which can be adjust-
ed while the inverter is in RUN mode. Otherwise, the inverter must be in STOP
mode. Data shown in […] applies to 3-phase inverters.
XX Function
01 Input frequency reference
Output
Hz
t
ON
X2-P24
Max. freq.
ON
FWD-P24
ON ON
X1-P24
0
ON
ON
ON
** *
Output
Hz
t
X2-P24
Max. freq.
ON
FWD-P24
X1-P24
0
ON
**
ON
ON
ON
ON
**
**
ON
RAMPS: Default is Accel./Decel. 1. Accel./Decel. 2 if F43 = 0 and X4-P24 is ON
* Initial value = 0
F01 = 2
** Initial value = Previous value
F01 = 3
ON