Chapter 7 Usage of Functions
7-
53
Conversion method is as below
1) scaling conversion value (A/D conversion) = [(data of 0 ~ 20
) 800] x 4000/3200
example) in case of 8
input at range 0 ~ 20
before the scaling conversion : 8
/ 5
= 1600
after the scaling conversion : (1600 800) x 1.25 = 1000
2) scaling conversion value (D/A conversion) = [(data of 4 ~ 20
) x 3200/4000] + 800
example) in case of ‘ 1000 output at range 4 ~ 20
current output value before the scaling conversion : 1000 x 5
= 5
current output value after the scaling conversion : (1000 x 0.8) + 800 = 1600
1600 x 5
= 8