Application Note 17 of 31 Rev. 1.30
2022-03-01
Current Sensor TLI4971
Programming Guide and User Manual
*)
Standard setting datecode 2118 and later
Table 11 Functional description Address 42
hex
CRC calculation is byte by byte, starting from address 42
hex
. After reaching the
end of the EEPROM (address 51
hex
), the address 40
hex
to 41
hex
are append. The
CRC calculation is based on the polynomial x
8
+x
4
+x
3
+x
2
+1
V
REF_nom
= 1.65 V (±10% if ratiometricity is enabled)
standard setting
V
REF_nom
= 1.2 V (±10% if ratiometricity is enabled)
V
REF_nom
= 1.5 V (±10% if ratiometricity is enabled)
V
REF_nom
= 1.8 V (±10% if ratiometricity is enabled)
The bit enables the quiescent voltage to 1.5V in semi-differential.
Default is 0 (=disabled)
If the bit is set to one only failure indication is activated at the OCD2 channel.
Over current detection is not activated if the bit is set to one.
Default is 0 (= fault signal on both OCDs)
If the bit is set, the sensitivity is ratio metric to VDD respective to VREF in single-
ended mode. Default is 0 (=disabled)
The ratio-metric offset behavior of the quiescent voltage is activated if the bit is
set to one. Default is 0 (=disabled)
4.2 Programming Example
Table 12 will guide the user through a complete programming sequence.
After activating the interface the integrated intelligent state machine (ISM) has to be powered down. To avoid
unintended high current consumption during applying the programming voltage at the OCD2 pin, the error
indication has to be disabled by writing the disable failure indication command to the device.
Programming requires two single commands followed by the programming pulse. One sequence is required to
program the ones and one sequence to program the zeros into the EEPROM. All digital values are stored in the
EEPROM. Figure 12 gives timing and an exemplary description of the programming sequence.