13: Battery voltage calibration
Interface Setting
Parameter 2: Select “Add” or “Sub” function to adjust battery voltage
to real figure.
Parameter 3: the voltage range is from 0V to 9.9V and the default
value is 0V.
14: Charger voltage adjustment
Interface Setting
Parameter 2: you may choose Add or Sub to adjust charger voltage
Parameter 3: the voltage range is from 0V to 9.9V and the default
value is 0V.
NOTE:
*Before making voltage adjustment, be sure to disconnect all batteries
first to get the accurate charger voltage.
* Any modification should be suitable to battery specifications.
15: Inverter A voltage adjustment
Interface Setting
Parameter 2: you may choose Add or Sub to adjust inverter A voltage.
Parameter 3: the voltage range is from 0V to 9.9V and the default
value is 0V.
16: Inverter B voltage adjustment
Interface Setting
Parameter 2: you may choose Add or Sub to adjust inverter B
voltage*.
Parameter 3: the voltage range is from 0V to 9.9V and the default
value is 0V.
*It will display number 1 under or to represent inverter
B voltage.
17: Inverter C voltage adjustment
Interface Setting
Parameter 2: you may choose Add or Sub to adjust inverter C
voltage*.
Parameter 3: the voltage range is from 0V to 9.9V, the default value is
0V.
*It will display number 2 under or to represent inverter
C voltage.