73
INFOSEC UPS SYSTEM – 4 rue de la Rigotière – 44700 Orvault – France – www.infosec-ups.com
Hot Line Tel : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 – hotline@infosec.fr –12 13 AA 59 203 07
18: Output A voltage calibration
Interface Setting
Parameter 2: it always shows OP.V as output voltage.
Parameter 3: it shows the internal measurement value of the output A
voltage, and you can calibrate it by pressing Up or Down according to
the measurement from an external voltage meter. The calibration result
will be effective by pressing Enter. The calibration range is limited within
+/-9V. This function is normally used for parallel operation.
19: Output B voltage calibration
Interface Setting
Parameter 2: it always shows OP.V as output voltage*.
Parameter 3: it shows the internal measurement value of the output B
voltage, and you can calibrate it by pressing Up or Down according to
the measurement from an external voltage meter. The calibration result
will be effective by pressing Enter. The calibration range is limited within
+/-9V. This function is normally used for parallel operation.
*It will display number 1 under to represent the output B
voltage.
20: Output C voltage calibration
Interface Setting
Parameter 2: it always shows OP.V as output voltage.
Parameter 3: it shows the internal measurement value of the output C
voltage, and you can calibrate it by pressing Up or Down according to
the measurement from an external voltage meter. The calibration result
will be effective by pressing Enter. The calibration range is limited within
+/-9V. This function is normally used for parallel operation.
*It will display number 2 under to represent the output C
voltage.