Installation manual
First operational test 33
Chapter
5
First operational test
A procedure is provided for an operational test on the Prime system after installation. The test
consists in the violation of a "Delayed" type zone.
This procedure must be carried out only after the complete installation of the Prime control
panel and of all the components that make up the entire installation. To do this it is advisable
to follow the instructions provided in Chapter 4, First power up.
1. Make sure all partitions are in stand-by status.
This status is signalled on the blue LED on the keypad or the blue icon on the Alien key-
pad when the latter is ON solid.
2. Enter the control panel programming phase and program the partition you intend to
violate.
Via softwareTo program the zone to be tested, click on the System Layout button on the menu on the
left. A graphic representation of the control panel board and a list of configured peripherals is
available in the section on the right (refer to the software manual, paragraph 5-2 Preparing a
system layout).
By double clicking on the terminal concerned you will enter the terminal programming phase.
Set “Delayed” as the “Type”.
Via keypad
Type in Code
(Installer)
, PROGRAMMING Terminals,
select the terminal concerned
or
Type-in Code
(Installer)
, PROGRAMMING Zones,
select the zone associated with the terminal concerned
Once the section has been accessed, set the “Type” as “Delayed”.
3. Set up the telephone dialer to provide voice signalling of violation.
Via softwareTo program voice signalling via the telephone communicator, click on the Telephone button in
the menu on the left to display a list of available numbers in the section on the right.
By selecting the telephone number “1” from the list, you can modify the parameters. In this
case it is necessary to enter the number to call and set the “Type” as “Voice”.
Via keypad
Type in Code
(Installer)
, PROGRAMMING Telephone, Selected number, "NUMBER 001".
Once in this section it is necessary to enter the number to call and set the “Type” as “Voice”.
4. Exit the programming phase and carry out an Away Arming operation.
If the default programming has not been changed, it can be carried out as follows:
Via keypadActivate the “Arm/Disarm” shortcut (shortcut no. 1) associated with the button shown
on the display.
Via Alien
interface
Press the Scenarios button. This section provides a list of the scenarios which can be
activated by means of the ACTIVATE button.
5. Wait until the “Exit Time” expires (30 seconds by default).
The keypads will emit a series of pulses (3 pulses + 5-second pause, 4 short pulses +
5-second pause during the last 20 seconds of the exit time).
6. Violate the programmed zone.
ENTRY TIME
7. Being a “Delayed” type zone, the “Entry Time” will begin (30 seconds by default).
The keypads will emit a series of pulses (8 pulses + 5 second pause).
TEST ALARM
SIGNALLING
8. If the Arming scenario is still active when the entry time expires, alarm signalling will
trigger:
Terminal xyz
Description
Partitions
Type
NUMBER 001
Number
Description
Type