Do you have a question about the Innotech Micro2000 M2K02 and is the answer not in the manual?
Details on voltage and power consumption requirements for the controller.
Specifies the types of sensors and digital inputs supported by the controller.
Details the voltage-free relay contacts and their resistive/inductive ratings.
Identifies terminals on the control station for sensor, digital input, and power.
Identifies terminals on the controller for power, earth, and neutral supply.
Specifies the common and normally open contacts for output relays.
Details terminals for power, comms, and ground connection to the control station.
Specifies storage, operating, and sensor input temperature ranges.
Indicates a communication issue between controller and control station.
Indicates an open circuit in the room temperature detector.
Indicates no flow signal feedback from the Pump Interlock Module.
Input for reading the current room temperature.
Configurable input for Door Switch, AC Fault, External Disable, or After Hours.
Input for the Pump Interlock Verify Signal.
Controls the fan with 16A resistive / 6A inductive rating.
Controls heating elements with 10A resistive / 6A inductive ratings.
Controls cooling stages with 2A resistive / 0.5A inductive ratings.
Enables or disables programmed schedules.
Controls After Hours mode and manual overrides.
Allows overriding programmed schedules for manual control.
Displays current time or selects Vent/Condition mode.
Procedure to enter the controller's programming mode.
How to select and adjust controller parameters.
Method to save programmed settings by holding the Time button.
Adjusts the temperature sensor reading offset.
Sets the lowest allowable temperature setpoint.
Sets the highest allowable temperature setpoint.
Defines the temperature range around the setpoint to prevent cycling.
Sets the differential for heating and cooling.
Duration the unit runs for after-hours operation.
Enables or disables manual adjustment of the After Hours timer.
Period the fan runs after heating shutdown to remove residual heat.
Minimum time the compressor must remain off before restarting.
Selects Electric Heat (EDH) or Reverse Cycle (REV) operation mode.
Selects heat relay energization for heating (HEA) or cooling (COOL).
Enables fan cycling with heating or continuous fan operation.
Configures display to show setpoint or current temperature.
Enables or disables the Time Clock functions.
Assigns functions to Input 2: Door, AC Fault, Disable, or After Hours.
Duration a door must remain open to be registered.
Temperature band for resetting door-related standby mode.
Duration the condenser water pump runs after call signal removal.
Diagram showing standard wiring for the control station.
| Controller Type | Programmable Logic Controller (PLC) |
|---|---|
| Power Supply | 24V DC |
| Inputs | 16 Digital, 8 Analog |
| Outputs | 16 Digital, 4 Analog |
| Ethernet | 10/100 Mbps |
| Digital I/O | 16 inputs / 16 outputs |
| Analog Inputs | 8 channels |
| Analog Outputs | 4 channels |
| Weight | 0.5 kg |
| Communication | Ethernet, USB |
Loading...