- 6 -
harmonics, the temperature rise, noise and vibration of the motor will be higher 
than those when it runs at standard frequency. 
1.2.4 Voltage-sensitive Device or Capacitor Improving Power Factor at the 
Output Side 
Since the servo driver output is PWM wave, if the capacitor for improving the 
power factor or voltage-sensitive resistor for lightning protection is mounted at 
the output side, it is easy to cause instantaneous over current in the servo 
driver, which may damage the servo driver. It is recommended that such 
devices not be used. 
1.2.5 Switching Devices like Contactors Used at the Input and Output terminal 
If a contactor is installed between the power supply and the input terminal of 
the driver, it is not allowed to use the contactor to control the startup/stop of the 
driver. If use of such contactor is unavoidable, it shall be used with interval of at 
least one hour.    Frequent charge and discharge will reduce the service life of 
the capacitor inside the driver.    If switching devices like contactor are installed 
between the output end of the driver and the motor, it shall ensure that the 
on/off operation is conducted when the driver has no output. Otherwise the 
modules in the driver may be damaged. 
1.2.8 Use under voltage rather than rated voltage   
If the driver is used outside the allowable working voltage range as specified in 
this manual, it is easy to damage the devices in the driver.     
When necessary, use the corresponding step-up or step-down instruments to 
change the voltage.   
1.2.7 Change Three-phase Input to Two-phase Input 
It is not allowed to change the IS300 series three-phase servo driver into 
two-phase one.    Otherwise, it may cause fault or damage to the servo driver. 
1.2.8 Lightning Protection 
Servo driver of the series  has lightning over current protection device, and 
has certain self-protection capacity against the lightning.  In applications 
where lightning occurs frequently, the user shall install additional protection 
devices at the front-end of the driver.   
1.2.9 Altitude and Derating 
In areas with altitude of more than 1,000 meters, the cooling effect of the driver 
may turn poorer due to rare air. Therefore, it needs to derate the driver for use. 
Please contact our company for technical consulting in case of such condition.