2 Wiring
- 12 -
•
DIP switch setting
Filter Selection Denition Address Setting Value Frequency Dividing
Coefcient
DIP Switch
8 7 6 5 4 3 2 1
0 0 Non-self-
adaptive lter
0 0 0 0 0 0 Reserved No output
Filter
selection
Frequency dividing
coefficient setting
ON
1
2
3
4
5
6
7
8
DIP
Low bits
High bits
0 0 0 0 0 1 1 Frequency divided by 1
0 1 Self-adaptive
lter
0 0 0 0 1 0 2 Frequency divided by 2
0 0 0 0 1 1 3 Frequency divided by 3
1 0 Fixed inter-
lock
���
1 1 1 1 0 1 61 Frequency divided by 61
1 1 Automatic
inter-lock
1 1 1 1 1 0 62 Frequency divided by 62
1 1 1 1 1 1 63 Frequency divided by 63
•
Indicators
Indicator Indication State Description
D1/D2/D3 Encoder input signal
indicator
ON or ash The encoder has signal input�
OFF The encoder does not have signal input�
D6 Power indicator ON Normal�
OFF Power is not connected�
LED1 Encoder input signal
quality indicator
ON Input signal is slightly instable, which occurs when motor accelerates/
decelerates or encoder signal input suffers slight interference�
OFF Input signal is normal, speed is stable and there is no interference�
Flash slowly Input signal is moderately instable, which occurs when motor accelerates/
decelerates or encoder signal input suffers moderate interference�
Flash quickly Input signal is seriously instable, which occurs when motor accelerates/
decelerates quickly or encoder signal input suffers severe interference�
LED2 Signal processing
quality indicator
ON Signal is slightly instable, which occurs when motor accelerates/decelerates
or interference during signal input is not completely ltered (The number of
interference pulses that are not ltered is less than 10 per time unit).
OFF Signal processing is normal, speed is stable and there is no interference�
Flash slowly Signal is moderately instable, which occurs when motor accelerates/
decelerates or interference during signal input is not completely ltered (The
number of interference pulses that are not ltered is less than 30 per time unit).
Flash quickly Signal is seriously instable, which occurs when motor accelerates/decelerates
or interference during signal input is not completely ltered (The number of
interference pulses that are not ltered is more than 30 per time unit).
LED3 Inter-lock state
indicator
ON Inter-lock enabled�
OFF Inter-lock disabled�
LED4 System state indicator ON Normal�
OFF The system is not operating or abnormal�
Flash The encoder cable breaks�