4�1 Hydraulic Application Setup Flowchart
Start Para� Parameter name Default Commissioning
Disable servo drive
Note: usually if any DI is set as forward or reverse run and the signal is active, then
some operations cannot succeed, such as restoring parameters, changing command
source, which are necessary steps for setup� So it’s seriously recommended to
disable servo drive at the beginning of commissioning�
Restore parameters FP-01 Parameter operation 0 1
0: no operation
1: restore factory parameters
Note: usually users have no idea what parameters have been changed, so it’s
seriously recommended to restore parameters to default at the beginning of
commissioning�
Set motor parameters Motor nameplate
F1-01 Rated motor power Model dependent
Unit: kW
F1-02 Rated motor voltage Model dependent
Unit: V
Note: please follow motor technical specications to set this parameter, otherwise
motor would probably run with vibration�
F1-03 Rated motor current Model dependent
Unit: A
F1-04 Rated motor frequency Model dependent
Unit: Hz
Note: please follow motor nameplate to set this parameter, otherwise motor auto-
tuning would fail and get E45� Here is the formula for motor frequency:
Frequency = number of motor poles * speed (rpm) / 120�
F1-05 Rated motor speed Model dependent
Unit: rpm�