4 Quick Setup
- 21 -
Continued Para� Parameter name Default Commissioning
Set AI1 range: pressure command F4-18 AI curve 1 minimum input 0�00 0�00
-11�00 to11�00 v;
F4-19 Corresponding setting of AI1minimum
input
0�0 0�0
-100�0% to 100�0%
Note: 0v pressure command is designed by press plc to represent 0%
pressure�
F4-20 AI1 maximum input 10�00 5�00
-11�00 to 11�00 v
F4-21 Corresponding setting of AI1maximum
input
100�0 100�0
-100�0% to 100�0%
Set AI2 range: ow command F4-23 AI curve 2 minimum input 0�00 0�00
-11�00 to11�00 v;
F4-24 Corresponding setting of AI2 minimum
input
0�0 0�0
-100�0% to 100�0%
F4-25 AI2 maximum input 10�00 10�00
-11�00 to 11�00 v
F4-26 Corresponding setting of AI2 maximum
input
100�0 100�0
-100�0% to 100�0%
Set AI3 range: pressure feedback F4-28 AI curve 3 minimum input 0�00 0�00
-11�00 to11�00 v;
F4-29 Corresponding setting of AI3minimum
input
0�0 0�0
-100�0% to 100�0%
F4-30 AI3 maximum input 10�00 10�00
-11�00 to 11�00 v
F4-31 Corresponding setting of AI3maximum
input
100�0 100�0
-100�0% to 100�0%
Note: 10v pressure feedback represents 100% pressure feedback� This is
related to A3-03�
Note: AI 1 is xed as pressure command input, AI2 is xed as speed/ow command input, and AI3 is xed as pressure sensor
feedback input. This conguration can’t be changed!
Continued Para� Parameter name Default Commissioning