5 Parameter Table
- 37 -
Para� No� Para� Name Setting Range Unit Default Property
FC-42 Correspondent value of AI2 point 1
input
-100�0% to 100�0% 0�1% 10�0%
☆
FC-43 AI2 point 2 input -11�00 to 11�00 V 0�01 V 2�00v
☆
FC-44 Correspondent value of AI2 point 2
input
-100�0% to 100�0% 0�1% 20�0%
☆
FC-45 AI2 point 3 input -11�00 to 11�00 V 0�01 V 3�00v
☆
FC-46 Correspondent value of AI2 point 3
input
-100�0% to 100�0% 0�1% 30�0%
☆
FC-47 AI2 point 4 input -11�00 to 11�00 V 0�01 V 4�00v
☆
FC-48 Correspondent value of AI2 point 4
input
-100�0% to 100�0% 0�1% 40�0%
☆
FC-49 AI2 point 5 input -11�00 to 11�00 V 0�01 V 5�00v
☆
FC-50 Correspondent value of AI2 point 5
input
-100�0% to 100�0% 0�1% 50�0%
☆
FC-51 AI2 point 6 input -11�00 to 11�00 V 0�01 V 6�00v
☆
FC-52 Correspondent value of AI2 point 6
input
-100�0% to 100�0% 0�1% 60�0%
☆
FC-53 AI2 point 7 input -11�00 to 11�00 V 0�01 V 7�00v
☆
FC-54 Correspondent value of AI2 point 7
input
-100�0% to 100�0% 0�1% 70�0%
☆
FC-55 AI2 point 8 input -11�00 to 11�00 V 0�01 V 8�00v
☆
FC-56 Correspondent value of AI2 point 8
input
-100�0% to 100�0% 0�1% 80�0%
☆
FC-57 AI2 point 9 input -11�00 to 11�00 V 0�01 V 9�00v
☆
FC-58 Correspondent value of AI2 point 9
input
-100�0% to 100�0% 0�1% 90�0%
☆
FC-59 Maximum AI2 input -11�00 to 11�00 V 0�01 V 10�00 V
☆
FC-60 Correspondent value of maximum
AI2 input
-100�0% to 100�0% 0�1% 100�0%
☆
Group FD: Bus communication and PC Software Setting
FD-00 Baud rate 0: 300 bps
1: 600 bps
2: 1200 bps
3: 2400 bps
4: 4800 bps
5: 9600 bps
6: 19200 bps
7: 38400 bps
8: 57600 bps
9: 115200 bps
1 5
☆
FD-01 Data format symbol 0: no parity check (8-n-2)
1: even parity check
2: odd parity check
3: no parity check (8-n-1)
1 0
☆
FD-02 Local address 0 to 247 1 1
☆
FD-03 Response delay 0 to 20 ms 1 ms 2 ms
☆
FD-04 Communication timeout 0�0s to 60�0s 0�1s 0�0s
☆
FD-30 PC software communication enable 0: Disable
1: enable
1 0�0
☆
FD-31 Channel 1 selection 0 to 999 1 10
☆