6 Parameter Table
 
 
 
 
6
- 99 -
DI/DO Function Denitions
No.
Function 
Symbol
Function Name Description Remarks
Input Function Description
FunIN.1 S-ON Servo ON
Invalid: Servo motor disabled
Valid: Servo motor enabled
The logic of the corresponding 
terminal needs to be set to 
level valid.
The change of the 
corresponding DI or VDI or 
terminal logic takes effect only 
after power-on again.
FunIN.2 ALM-RST
Fault and 
warning reset 
(edge valid)
Invalid: Disabled
Valid: Enabled
This DI function is edge valid 
rather than high/low level 
valid.
The servo drive can continue 
to operate after fault/warning 
reset.
When this function is allocated 
to a low-speed DI and logic of 
the DI is level valid, the servo 
drive will forcibly changes it to
edge logic. The valid level 
change must last for more 
than 3 ms; otherwise, the 
fault reset function becomes 
invalid. 
Do not allocate this function to 
high-speed DI. Otherwise,
fault/warning reset will be 
invalid.
FunIN.3 GAIN-SEL Gain switchover
H08-09 = 1:
Invalid: Speed control loop 
being PI control
Invalid: Speed control loop 
being P control
H08-09 = 2:
Invalid: Fixed at 1st gain
Valid: Fixed at 2nd gain
It is recommended that the 
logic of the corresponding 
terminal be set to level valid.
FunIN.4 CMD-SEL
Main/Auxiliary 
reference 
switchover
Valid: Current running 
reference being A
Invalid: Current running 
reference being B
It is recommended that the 
logic of the corresponding 
terminal be set to level valid.
FunIN.5 DIR-SEL
Multi-reference 
direction
Invalid: Default reference 
direction
Valid: Reverse to reference 
direction
It is recommended that the 
logic of the corresponding 
terminal be set to level valid.
FunIN.6 CMD1
Multi-reference 
switchover 1
Used to select one from the 16 
references
It is recommended that the 
logic of the corresponding 
terminal be set to level valid.