Page 31 of 43
9 Group F8: Auxiliary Functions
Function
Code
Parameter Name
Setting Range
Unit
Default
Commission
F8-00
JOG running
frequency
0.00 to Max. frequency
Hz 2.00
F8-01
JOG acceleration time
0.0 to 6500.0
s
20.0
F8-02
JOG deceleration time
0.0 to 6500.0
s
20.0
F8-03
Acceleration time 2
0.0 to 6500.0
s
Model
dependent
F8-04
Deceleration time 2
0.0 to 6500.0
s
Model
dependent
F8-05
Acceleration time 3
0.0 to 6500.0
s
Model
dependent
F8-06
Deceleration time 3
0.0 to 6500.0
s
Model
dependent
F8-07
Acceleration time 4
0.0 to 500.0
s
Model
dependent
F8-08
Deceleration time 4
0.0 to 6500.0
s
Model
dependent
F8-09
Frequency Jump 1
0.00 to Max. frequency
Hz
0.00
F8-10
Frequency Jump 2
0.00 to Max. frequency
Hz
0.00
F8-11
Frequency jump
amplitude
0.00 to Max. frequency
Hz
0.00
F8-12
Forward/Reverse
rotation dead-zone
time
0.0 to 3000.0
s 0.0
F8-13
Reverse control
0: Enabled
1: Disabled
N.A.
0
F8-14
Running mode when
set frequency lower
than frequency lower
limit
0: Run at frequency lower limit
1: Stop
2: Run at zero speed
N.A.
0
F8-15
Droop control
0.00 to 10.00
Hz
0.00
F8-16
Accumulative
power-on time
threshold
0 to 65000
h 0
F8-17
Accumulative running
time threshold
0 to 65000
h
0
F8-18
Startup protection
0: No
1: Yes
N.A. 0
F8-19
Frequency detection
value (FDT1)
0.00 to Max. frequency
Hz
50.00
F8-20
Frequency detection
hysteresis
(FDT1hysteresis )
0.0 to 100.0 (FDT1 level)
% 5.0
F8-21
Detection range of
frequency reached
0.00 to 100 (Max. frequency)
%
0.0
F8-22
Frequency Jump
during acceleration/
deceleration
0: Disabled
1: Enabled
N.A.
0
F8-27
Terminal JOG
preferred
0: Disabled
1: Enabled
N.A. 0
F8-28
Frequency detection
value (FDT2)
0.00 to Max. frequency
N.A.
50.00
F8-29
Frequency detection
hysteresis (FDT2)
0.0 to 100.0 (FDT2 level)
%
5.0
F8-30
Detection value 1 of
any frequency
reaching
0.00 to Max. frequency
Hz
50.00
F8-31
Detection amplitude 1
of any frequency
reaching
0.0 to 100.0 (Max. frequency)
%
0.0
F8-32
Detection value 2 of
any frequency
reaching
0.00 to Max. frequency
Hz
50.00
efesotomasyon.com