Function
Code
Parameter Name
Setting Range
Unit
Default
Commission
F8-33
Detection amplitude 2
of any frequency
reaching
0.0 to 100.0 (Max. frequency)
%
0.0
F8-34
Zero current detection
level
0.0 to 300.0
(rated motor current as 100%)
% 5.0
F8-35
Zero current detection
delay
0.01 to 600.00
s
0.10
F8-36
Output overcurrent
threshold
0.0 (no detection)
0.1 to 300.0 (rated motor current)
%
200.0
F8-37
Output overcurrent
detection delay
0.00 to 600.00
s 0.00
F8-38
Detection value 1 of
any current reached
0.0 to 300.0 (rated motor current)
%
100.0
F8-39
Detection amplitude 1
of any current reached
0.0 to 300.0 (rated motor current)
%
0.0
F8-40
Detection value 2 of
any current reached
0.0 to 300.0 (rated motor current)
% 100.0
F8-41
Detection amplitude 2
of any current reached
0.0 to 300.0 (rated motor current)
%
0.0
F8-42
Timing function
0: Disabled
1: Enabled
N.A.
0
F8-43
Timing duration source
0 to 3
N.A.
0
F8-44
Timing duration
0.0 to 6500.0
min
0.0
F8-45
AI1 input voltage lower
limit
-11.00 to F8-46
V 3.10
F8-46
AI1 input voltage
upper limit
F8-45 to 11.00
V
6.80
F8-47
Module temperature
threshold
0 to 100
Ԩ
75
F8-48
Cooling fan working
mode
0: Fan working during running
1: Fan working continuously
N.A. 0
F8-49
Wakeup frequency
Dormant frequency (F8-51) to Max. frequency
(F0-10)
Hz
0.00
F8-50
Wakeup delay
0.0 to 6500.0
s
0.0
F8-51
Hibernating frequency
0.00 to wakeup frequency (F8-49)
Hz
0.00
F8-52
Hibernating delay
0.0 to 6500.0
s
0.0
F8-53
Current running time
reached
0.0 to 6500.0
min
0.0
F8-54
Output power
correction coefficient
0.0 to 200.0
% 100.0