9 Group F9: Fault And Protection
Function
Code
Parameter Name
Setting Range
Unit
Default
Commission
F9-00
Motor overload
protection
0: Disabled
1: Enabled
N.A. 1
F9-01
Motor overload
protection gain
0.20 to 10.00
N.A.
1.00
F9-02
Motor overload
pre-warning coefficient
50 to 100
%
80
F9-03
Overvoltage stall gain
0 to 100
N.A.
0
F9-04
Overvoltage stall
protective voltage
120 to 150
% 130
F9-05
Overcurrent stall gain
0 to 100
N.A.
20
F9-06
Overcurrent stall
protective current
100 to 200
%
150
F9-07
Short-circuit to ground
upon power-on
0: Disabled
1: Enabled
N.A.
1
F9-09
Auto reset times
0 to 20
N.A.
0
F9-10
DO action during fault
auto reset
0: Not act
1: Act
N.A. 0
F9-11
Delay of fault auto
reset
0.1 to 100.0
s
1.0
F9-12
Power input phase
loss protection
0: Disabled
1: Enabled
N.A.
0
F9-13
Power output phase
loss protection
0: Disabled
1: Enabled
N.A. 1
F9-14
1st fault type
0 to 51
N.A.
N.A.
F9-15
2nd fault type
0 to 51
N.A.
N.A.
F9-16
3rd (latest) fault type
0 to 51
N.A.
N.A.
F9-17
Frequency upon 3rd
fault
N.A.
N.A.
N.A.
F9-18
Current upon 3rd fault
N.A.
N.A.
N.A.
F9-19
Bus voltage upon 3rd
fault
N.A.
N.A.
N.A.
F9-20
Input terminal status
upon 3rd fault
N.A.
N.A. N.A.
F9-21
Output terminal status
upon 3rd fault
N.A.
N.A.
N.A.
F9-22
AC drive status upon
3rd fault
N.A.
N.A.
N.A.
F9-23
Power-on time upon
3rd fault
N.A.
N.A. N.A.
F9-24
Running time upon 3rd
fault
N.A.
N.A.
N.A.
F9-27
Frequency upon 2nd
fault
N.A.
N.A.
N.A.
F9-28
Current upon 2nd fault
N.A.
N.A.
N.A.
F9-29
Bus voltage upon 2nd
fault
N.A.
N.A. N.A.
F9-30
Input terminal status
upon 2nd fault
N.A.
N.A.
N.A.
F9-31
Output terminal status
upon 2nd fault
N.A.
N.A.
N.A.
F9-32
Frequency upon 2nd
fault
N.A.
N.A. N.A.
F9-33
Current upon 2nd fault
N.A.
N.A.
N.A.
F9-34
Bus voltage upon 2nd
fault
N.A.
N.A.
N.A.
F9-37
Input terminal status
upon 1st fault
N.A.
N.A.
N.A.
F9-38
Output terminal status
upon 1st fault
N.A.
N.A. N.A.
efesotomasyon.com