Parameter Description MD280/MD280N User Manual
- 112 -
value is the initial value of the inverter frequency.
Maximum
frequency
Factory default
value
50.00 Hz
F0-04
Setup range 50.00Hz to 630.00Hz
It is used to set the maximum output frequency of the inverter.
Frequency upper limit
Factory
default value
0
0 F0-06 setting
1AI1
2AI2
F0-05
Setup
range
3
Pluse setting˄DI5˅
It is used to select the reference channel of frequency upper limit.
Frequency upper
limit
Factory
default value
50.00Hz
F0-06
Setup
range
Frequency lower limit˄F0-07˅ to maximum
frequency˄F0-04˅
It is used to set the frequency upper limit output by the inverter.
Frequency lower
limit
Factory
default
value
0.00Hz
F0-07
Setup range
0.00Hz to frequency upper limit ˄F0-06˅
It is used to set the frequency lower limit output by the inverter.
When the running frequency of the inverter is lower than the frequency
lower limit, it can select to run or stop the inverter at frequency lower limit.
Refer to F5-10 function code for details. I
Speed-up/speed-down time
unit
Factory default
value
0
0 s (second)
F0-08
Setup
range
1 m (minute)
It is used to select the unit of Speed-up/speed-down time of the inverter.It is
valid for speed-up time 1 ˄F0-09˅,speed-down time 1 ˄F0-10˅,speed-up
time 2 ˄F5-04˅and speed-down time 2 ˄F5-05˅.