MD280/MD280N User Manual             Parameter Description          
- 179 -
Speed-up/speed-down 
time of  the seventh 
segment of PLC 
Factory default 
value 
0 
0 Speed-up/speed-down 1 
F8-27 
Setup range 
1 Speed-up/speed-down 2 
Group F9 Reserved 
Group FA Communication Parameters 
Refer to MD280F Serial Communication Protocol for details.   
Group FB Overload and Protection 
Motor overload protection 
selection 
Factory 
default 
value 
1 
0˖ Invalid 
FB-00 
Setup 
range 
1˖ Valid 
0: Without motor overload 
protection function. It is 
recommended to install a 
thermal relay before the motor.   
1: The inverter has overload 
protection function for the 
motor. Refer to FB-01 and 
FB-02 for the protection setup. 
 
Motor overload 
protection gain 
Factory default 
value 
1.00 
FB-01 
Setup range    0.20 to 10.00 
 
In order to effectively protect the motor with different loads, it needs to set 
this parameter according to the overload capacity of the motor. The 
overload protection on motor forms an inverse time-lag curve. When the 
operating current of the motor reaches the current of 220%×FB-01 times 
the rated current of motor, it will report motor overload (ERR11) after it lasts 
one minute. When the operating current of the motor reaches the current of 
150%×FB-01 times the rated current of the motor, it will report motor 
overload (ERR11) after it lasts one minute.    The motor overload protection 
curve is as shown in Fig.6-25:   
 
 