Parameter Description              MD280/MD280N User Manual 
- 144 -
Group F4 Start/Stop Control 
Startup mode 
Factory default 
value 
0 
0 
Direct startup (When the DC brake 
time is non-zero value, it can perform 
DC brake before start.) 
F4-00 
Setup 
value 
1  Rotation velocity tracking startup 
0: Direct startup:   
When the DC brake time is zero, it starts at the startup frequency.   
When the DC brake time is non-zero value, it can perform DC brake before 
start. It is suitable for the applications where small inertia may cause 
reverse rotation at the time of startup.   
1: Rotation velocity tracking startup: The inverter firstly judges the rotation 
velocity and direction of the motor and then starts at the frequency 
corresponding to the tracked rotation velocity of the motor, and performs 
smooth startup of the motor in rotation without impact.   
It is suitable for the applications where large inertia is restarted due to 
transient power shutdown.   
In order to ensure the performance of the rotation velocity tracking startup, 
it needs set the motor parameters (Group F1) correctly.   
Rotation speed tracking mode
Factory default 
value 
0 
0  Start from stop frequency 
1  Start from zero speed 
F4-01 
Setup range
2  Start from maximum frequency 
In order to complete the rotation speed tracking process in the shortest 
period, it can select the mode of inverter tracking the rotation velocity of 
motor:  
0: Track downward from the frequency at the time of stop, which is 
generally selected at first.   
1: Track upward from zero frequency, which is used when the inverter is 
restarted upon long period of power shutdown.   
 