MD280/MD280N User Manual             Parameter Description          
- 145 -
2: Track downward from the maximum frequency, which is generally used 
for power generating load.   
Rotation velocity tracking 
fastness and slowness 
Factory 
default 
value 
20 
F4-02 
Setup range  1 to 100 
When it is in the mode of rotation speed tracking startup, it is used select 
the fastness and slowness of tracking the rotation speed. The higher the 
parameter value is, the faster the tracking velocity is, but too higher value 
may cause unreliable tracking. 
Startup frequency 
Factory 
default value
0.00Hz 
F4-03 
Setup range 
0.00Hz to maximum frequency 
˄F0-04˅ 
Startup frequency 
retention time 
Factory 
default value
0.0s 
F4-04 
Setup range  0.0s to 36.0s 
To ensure the torque at the time of startup proper startup frequency shall 
be set. In addition, in order to set up magnetic flux when waiting for the 
startup of the motor, the startup frequency shall remain for a certain period 
of time before accelerating to the setup frequency, as shown in Fig.6-10.   
If the frequency reference value (frequency source) is lower than the 
startup frequency, the inverter cannot start and will be in standby status.   
Example 1:   
F0-01=0 means the frequency source is digital reference.   
F0-03˙10.00Hz means the digital setup frequency is 10.00Hz.   
F4-03˙5.00Hz means the startup frequency is 5.00Hz.   
F4-04˙2.0s means that the startup frequency retention time is 2.0s.   
In this case, the inverter will be in the standby status and its output 
frequency is 0Hz.   
Example 2:   
F0-01=0 means the frequency source is digital reference.   
 