Parameter Description MD280/MD280N User Manual
- 114 -
“Speed-up/speed-down Selection Terminal” of function codes of Group
F2-00 to F2-04 for details.
Carrier
frequency
Factory default
value
Model dependent
F0-11
Setup range 0.5kHz to 16.0kHz
This function is used to adjust the carrier wave frequency of the inverter. By
adjusting the carrier wave frequency, the motor noise can be reduced, the
resonance of the mechanical system can be avoided, so that the leakage
current to the ground and the interference of the inverter can be reduced.
When the carrier wave frequency is low, the output current higher harmonic
component will be increased, the motor loss will be increased, and the
motor temperature rise will also increase.
When the carrier wave frequency is high, the motor loss is reduced, and
the motor temperature is reduced also, but the inverter loss and inverter
temperature rise will be increased, and thus the interference will be
increased.
The adjustment of carrier frequency will have the following influences on
the performance:
Carrier frequency Low ĺ High
Motor noise High ĺ Low
Output current
waveform
Poor ĺ Good
Motor temperature
rise
High ĺ Low
Inverter
temperature rise
Low ĺ High
Leakage current Low ĺ High
Radiation
interference
Low ĺ High
Running direction
Factory
default value
0
0 Consistent direction
F0-12
Setup range
1 Reverse direction
Modification of this parameter can change the rotary direction of the motor
without changing any other parameters, which is equivalent to the role of
efesotomasyon.com