Parameter Description MD280/MD280N User Manual
- 124 -
Action description:
Set the function code to 1 and press RUN key for confirmation, and then
the inverter will conduct static tuning.
Tuning operation description:
Select the command source (F0-00) as the command channel of the
operation panel.
Set correct motor parameter (F1-00 to F1-03˅˗
When it is set to 1, press ENTER key and “TUNE” will be displayed and
flashes. Press RUN key to conduct parameter tuning, and at this time the
displayed “TUNE” stops flashing. After the tuning is completed, the display
will return to the stop status interface.The tuning process can be stopped
by pressing the STOP key.
When the tuning is completed, the value of F1-11 will automatically restore
to 0.
Caution: Tuning is valid only in the keyboard control mode.
Oscillation
suppression mode
Factory default
value
Model dependent
F1-19
Setup vlaue 0 to 3
0˖Oscillation suppression is not dependent on no-load current, which is
valid only below 15Hz.
1: Oscillation suppression is dependent on no-load current, which is valid
by default.
2: Oscillation suppression is dependent on no-load current, which is valid
only below 15Hz.
3: Oscillation suppressions is dependent on no-load current, which is valid.