Parameter Description              MD280/MD280N User Manual 
- 126 -
Setup 
value
Function  Description 
reverse rotations. 
4 
Forward rotation 
Jog˄FJOG˅ 
5 
Reverse rotation 
Jog˄RJOG˅ 
The forward jog and reverse jog of the 
inverter are controlled via the external 
terminals. Refer to the descriptions of 
function codes F5-00, F5-01 and F5-02 
for the details of jog running frequency 
and jog speed-up/speed-down time. 
6 Terminal UP 
7 Terminal DOWN 
When command source (F0-01) is set as 
“Digital Setup”, the increase or decrease 
of the setup frequency is implemented 
through the external terminal. The 
increase/decrease velocity is set by 
F2-07. 
8 Free stop 
When this terminal command is valid, 
meaning that the inverter locks the output, 
the load will free stop according to the 
mechanical inertia. 
9 
Fault reset 
(RESET) 
When this terminal command is valid, 
inverter’s fault can be reset. 
The function is a valid pluse. 
10 
Pause during 
operation 
When this terminal command is valid, the 
inverter sets the way of stop according to 
F4-10 function code. If it is PLC running at 
this time, it will memorize the frequency 
and running time of the running phase at 
the pause time, during which the PLC 
does not count the time. 
11 
External fault 
normally open 
input 
12 
External fault 
normally closed 
input 
External fault signal can be inputted 
through the external terminal for 
monitoring fault of external equipments by 
inverter.When the inverter detects that 
external equipments occur fault, it will 
stop and report “ERR15” fault.The fault 
signal input can adopt either normally 
open or normally closed mode. 
The enxternal fault normally open input is 
selected, it may occur fault when the 
 