MD280/MD280N User Manual Parameter Description
- 135 -
time lasts, the stronger the interference immunity will become, but
adjustment response will be slow down; the shorter the filtering time lasts,
the faster the response will be, but the interference immunity will become
weak.In various application cases, the nominal value corresponding to
100% of analog reference will be different. Refer to specific application
description for the specific value.
C
orresponding Settings
(Frequency, etc.˅
C
orresponding Settings
(Frequency, etc.˅
Fig6-4 Corresponding relation between analog reference and setting value
AI2 minimum input
Factory
default
value
0.02V
F2-14
Setup range
0.00V to F2-16
Corresponding Setup of
AI2 minimum input
Factory
default
value
0.0%
F2-15
Setup range
-100.0% to 100.0%
AI2 maximum input
Factory
default
value
10.00V
F2-16
Setup range
F2-14 to 10.00V
AI2 maximum input
corresponding setup
mode
Factory default
value
0
0 F2-18
F2-17
Setup range
1 Set by AI1