Parameter Description MD280/MD280N User Manual
- 182 -
Fig.6-26 Schematic Diagram for over current stall protection
䕧ߎ⬉⌕ Output current
䖛⌕༅䗳ֱᡸ⬉⌕⚍ Over current stall protection current points
䕧ߎ乥⥛ Output frequency
䆒ᅮ乥⥛ Setup frequency
ࡴ䗳䖛 Speed-up process
ᘦ䗳䖛 Constant speed process
ޣ䗳䖛 Speed-down process
ᯊ䯈 Time
Fig.6-26 Schematic Diagram for over current stall protection
Ground short circuit
protection upon
power-on
Factory default
value
1
0˖
Invali
d
FB-07
Setup
range
1˖
Valid
It determines whether the inverter will
check if the motor has ground short
circuit fault upon power-on. If this
function is valid, the inverter has
short-time output at the instance of
power-up.
FB-08
Load fault protection function
Factory
default value
0