MD280/MD280N User Manual Parameter Description
191
0 No operation
1 Restore the factory default value
Setup
range
2 Clear memory
0: No function.
1: The inverter restores all the parameters excluding the following parameters
to the factory default values:
1) Motor parameters (Group F1): F1-00 to F1-03, F1-15 and F1-16;
2) Accumulated running time (F7-12) and inverter module temperature
(FB-19);
3) Fault type parameters: FB-20 to FB-27;
4) User password: FP-00
2: clear memory: The inverter clears the fault records (FB-20 to F1-03) and
accumulated running time (F7-12) to zero.