6. Description of Parameters
- 110 -
6
6.2 Set Frequency Reference
The AC drive provides the following four methods to output the required frequency reference:
Ɣ
Main frequency reference
Ɣ
Auxiliary frequency reference
Ɣ
Main & auxiliary calculation
Ɣ
Command source + frequency reference setting channel
6.2.1 Set Main Frequency Reference
Main frequency reference has nine setting channels.
F0-03 selects a required channel to set the main frequency reference, described in the following
¿JXUH
Function Code Parameter Name Setting Range Default
F0-03
Main frequency
reference setting
channel selection
0: Digital setting (non-retentive at power down)
1: Digital setting (retentive at power down)
2: AI1
3: AI2
4: AI3
5: Pulse reference
6: Multi-reference
7: Simple PLC
8: PID reference
9:
Serial comms.
0