6. Description of Parameters
- 156 -
6
6.6.4 Fault Protection Action Selection
Function Code Parameter Name Setting Range Default
F9-47
Fault protection
action selection 1
Input phase loss (Err12):
Same as that of units position
Motor overload (Err11):
0: Coast to stop
1: Stop according to stop mode
2: Continue to run
Output phase loss (Err13):
Same as that of units position
Communication fault (Err16):
Same as that of units position
External fault (Err15):
Same as that of units position
00000
F9-48
Fault protection
action selection 2
EEPROM read-write fault (Err21):
0: Coast to stop
1: Stop according to stop mode
Encoder fault (Err20):
0: Coast to stop
1: Switch over to V/F control, stop
according to stop mode
2: Switch over to V/F control,
continue to run
Reserved
Accumulative running time
reached (Err26):
0: Coast to stop
1: Stop according to stop mode
2: Continue to run
Motor overheat (Err25):
0: Coast to stop
1: Stop according to stop mode
2: Continue to run
00000
Function Code Parameter Name Setting Range Default
F9-54
Frequency selection
for continuing to run
upon fault
0: Current running frequency
1: Frequency reference
2: Frequency upper limit
3: Frequency lower limit
4: Backup frequency upon abnormality
0
F9-55
Backup frequency
upon fault
0.0% to 100.0% (max. frequency) 100.0%
7KHVHIXQFWLRQSDUDPHWHUVGH¿QHUXQQLQJIUHTXHQF\RIWKH$&GULYHZKHQ³&RQWLQXHWRUXQ´LV
selected at occurrence of fault.